The FX2200 ranges of conventional control panels provide a solution to any conventional system requirement. The advanced features include a simple “one-shot” user test facility, class change contacts, battery voltage alarms and charger temperature compensation, all included as standard to ensure ease of use and high reliability.
Attention to detail is emphasised by the neat log book holder feature, allowing essential records to be stored close to hand, ready for quick reference.
For larger installations, custom configuration of the panels offers even greater flexibility, allowing project specific requirements to be easily met, in a competitive and cost effective package.
Meets EN standards EN54 parts 2 & 4, and EN 50130-4
USER-FRIENDLY
Walk-test functionality facilitates system testing
FLEXIBLE
High-specification panel that suits a wide-range of conventional fire projects
Cost-effective and versatile, a conventional panel for multiple applications
Suitable for small to medium-sized commercial buildings, such as hotels, restaurants, retail units, care homes, warehouses and supermarkets, the range offers easy customer configuration by design.
Reliable and easy-to-use
Boasting as standard, simple “one-shot” user test facility, class change contacts, battery voltage alarms and charger temperature compensation making installation more flexible and ongoing testing quicker.
Instant recognition, for fire and non-fire applications
Suitable for small to medium-sized commercial buildings, such as hotels, restaurants, retail units, care homes, warehouses and supermarkets, the range offers easy customer configuration by design.
BiWire Flexi - Your simpler, cheaper, more versatile choice for new & old fire projects
Whether fitting out a building extension, retrofitting an outdated system or looking to benefit from the cost and time benefits of two-wire technology on a new build and want to utilise certain conventional devices; BiWire Flexi gives you the power to adapt the system to the site.
Features
. 2, 4 or 8 zones panels
. Flexible, high specification system
. Surface or semi-flush mounting
. Simple “one-shot” auto-reset user test facility
. Maintenance free poly switch circuit protection, with auto reset
. Class change and programmable fire/fault relay as standard
. Batteries not included
Benefits
. Suitable for a large range of projects
. No fuses required
. Discreet panel design for incorporation in to any decor
. Numerical access code (no lost keys)
. Easy to maintain/service
PRODUCT CODES
TECHNICAL SPECIFICATIONS
PRODUCT CODES
2 Zone Panel
FX2202CPD
4 Zone Panel
FX2204CPD
Steel Recessing Back Box
FX22003300 MB
Fire Alarm System Log Book
MFALOG
TECHNICAL SPECIFICATIONS
Description:
2 / 4 Zone Control Panel
Standards:
EN54 Pt2 & Pt4 1998 EN50130 Pt4 1996, EN50130 Pt4
Number of Zones:
2, 4
Detectors per Zone:
30
Number of Alarm Circuits:
02-Apr
Alarm Circuit Load:
2 Zone: 150mA per circuit, 0.3A total 4 Zone: 400mA per circuit, 0.8A total
End Of Line Devices:
Detection circuits: EOLM-1 monitoring unit Alarm lines: 6.8KΩ resistor
Auxiliary Fire Signal / Fault Output:
1A 24Vdc single pole changeover contacts
Auxiliary DC Output:
24Vdc fused. 30mA
Repeater Port:
Yes
Mains Input Voltage:
230Vac -15% +10%
System Operating Voltage:
24Vdc
Standby Duration:
24 hours
Battery (Sealed Lead Acid):
2 Zone: 1 x 3.2Ah 4 Zone: 1 x 3.2Ah
Recharge Period:
24 hours
Operating Temperature:
-5°C to +40°C
Humidity (Non-condensing):
0 to 75% RH
Construction:
Polycarbonate housing & back box
Dimensions (HxWxD):
Surface: 270mm x 332mm x 90mm Recessed: 279mm x 332mm x 122mm
Weight (Including batteries):
2 Zone: 5.2kg 4 Zone: 5.8kg
Ingress Protection:
IP30
Cable Entry:
Top: 12x20mm entries with blanking plugs, rear cable entry aperture