Conventional 8 Zone Control Panel – EFCV8Z

Eaton’s 8 zone conventional fire system panel delivers a straightforward, intuitive interface that makes programming and maintenance simple.

Approved to EN54-2&4, it offers a comprehensive set of functionalities in a modern, robust and discreet enclosure. Its appearance and performance make the panel well suited for life safety notification in a wide variety of small to medium sized buildings, particularly schools, warehouses, retail stores and office buildings.

With the addition of an isolator barrier the panel has the additional flexibility to monitor standard or intrinsically safe conventional zone circuits, making it suitable for industrial applications.

 

Additional information
Order Code

EFCV8Z

System

Addressable

Product Type

Conventional Control Panels

Contact me about this Product
Name
Email
Phone
Enquiry

TESTING

One man test facility

INTERLINK RELAY

Function for connecting 2 panels

ISOLATOR BARRIER

Zones are switchable

Switch between normal and intrinsically safe modes for peace of mind in industrial applications

The 8 zone panel offers a standard mode and an intrinsically safe mode. In the standard mode, the maximum loading is 32 detectors and manual call points per zone, in the intrinsically safe mode the maximum loading switches to 10 detectors and manual call points per zone. With the addition of an isolator barrier, the panel has the flexibility to monitor standard or intrinsically safe conventional zone circuits, making it suitable for industrial applications.

Intelligent design for an intelligent panel

The aesthetically pleasing control panel has a modern and discreet enclosure to ensure the device does not look out of place in public areas. The device accommodates simple system testing by a single fire alarm technician and its interlink relay gives greater flexibility to configure zones to work in ATEX areas using an isolator barrier.

Instant recognition, for fire and non-fire applications

Suitable for small to medium-sized commercial buildings, such as hotels, restaurants, retail units, care homes, warehouses and supermarkets, the range offers easy customer configuration by design.

BiWire Flexi - Your simpler, cheaper, more versatile choice for new & old fire projects

Whether fitting out a building extension, retrofitting an outdated system or looking to benefit from the cost and time benefits of two-wire technology on a new build and want to utilise certain conventional devices; BiWire Flexi gives you the power to adapt the system to the site.

Benefits

  • . Flexibility to configure zones to work in ATEX areas using an isolator barrier
  • . Simple system testing by a single fire alarm technician
  • . Capability to sound class change bell in schools
  • . Interlink relay allows for greater system flexibility
  • . Comprehensive protection for safety of building occupants
  • . Panel not out of place in public areas

Features

  • . Zones switchable between standard conventional and intrinsically safe zones (using isolator barrier)
  • . One man test facility
  • . Class change input
  • . Interlink relay functionality for connecting 2 panels together
  • . Supports an expansion card for Fire Routing Equipment, Fire Protection Equipment and fire relays per zone.
  • . Modern and discreet enclosure
  • . Batteries not supplied
8 Zone Conventional PanelEFCV8
End of Line ModuleEOLM-1
8 Zone Relays + FRE/FPEBWOB8Z
Input Voltage Range:18.75 – 30.7V
Maximum Current Drawn from Battery:2.7A
Number of Zones:8
Maximum Loading per Zone:Standard Mode: 32 detectors and manual call points
Intrisically Safe Mode: 10 detectors and manual call points
Standby Zone Voltage (Vmin – Vmax):19Vdc – 23Vdc
Alarm Zone Voltage (Vmin – Vmax):31Vdc – 33Vdc
Fuse Protection Per Zone:250mA PTC
End of Line A Termination:Standard Conventional Zones – EOLM-1 Only
Intrinisically Safe Zones – SKI Resistor
Number of Sounder Circuits:230V Ah +10%/-15% 50Hz
Maximum Loading per Circuit:250mA
Fuse Protection per Circuit:250mA PTC
End of Line B Termination:6K8 Resistor
Unmonitored Outputs – Fire, Fault, Interlink Relay:Type – Volt-Free, Single Pole Double Throw
Rating – 30Vdc, 1A
Fuse – 500mA PTC
Auxilliary Output:V – 18.15-30.7V
Imax – 50mA
Fuse – 50mA PTC
Unmonitored Inputs: Class ChangeOpen Circuit – Normal Panel Operation
Short Circuit – Activate All Sounders
Repeater Port (use of this port is outside the scope of EN54):Type – RS485
Nodes – 1
Operating Temperature:-5°C to +40°C
Relative Humidity (Non-condensing):93% +/-3%
IP Rating:IP30
Dimensions (WxHxD):375mm x 366mm x 134mm
Weight (excluding batteries):2.25Kg
Materials:PC ABS Front and Rear
Standards:EN54 Part 2 CIE & Part 4 PSE, BS5839 Part 1