Dual Channel LonWorks BMS Interface – EC200

The control panels on a Cooper fire network communicate using pre-configured network variables and cannot normally be used with a BMS where binding is required.

The (EC200) dual-channel LonWorks BMS interface is an “add-on” to the network which translates the pre-configured network variables to a set of un-configured network variables which can then be bound to a BMS, giving full access to the fire network data.

The gateway has 2 channels:
Channel 1 – connects to the Cooper fire network
Channel 2 – connects to the BMS

Additional information
Order Code

EC200

System

Addressable

Product Type

Addressable Network and BMS

Contact me about this Product
Name
Email
Phone
Enquiry

COMPREHENSIVE

Full range to suit addressable fire system requirements

SOFT ADDRESSING

Helps monitor & manage building management systems (BMS)

USER-FRIENDLY

Easy to install, use and diagnose issues

Control you Eaton’s fire system from a building management system with no need for binding

The LonsWork BMS interface allows Eaton’s fire network to be controlled by a LonWorks enabled building managment system (BMS) with no need for binding. It features a 32 message input buffer and compact DIN rail mounting enclosure. It can also enables connection to a third party BMS system.

Benefits

• Compact DIN rail mounting enclosure
• Fully compatible with Cooper fire network (no need for binding)
• Open protocol to 3rd party BMS system

Features

• Allows a Cooper fire network to be controlled by a LonWorks enabled BMS
• Uses Echelon FT5000 smart transceivers for high noise immunity
• 32 message input buffer

Benefits

• Extends Cooper network
• Plug and play
• No configuration required
• Simple to use

Plug and play Lon network booster

Used for Eaton network extension, the plug and play installation capability of the EC540 allows network connection without any further configuration. It uses smart switch technology to automatically detect the bit rates of the connected channels,and learn the configuration of the network (domains, subnet / node addresses, group addresses).

Single Mode Lon to Fibre Optic AdaptorCFSL01
Dual Channel Lon to Fibre Optic AdapterCFSFL02
Dual Channel LonWorks BMS InterfaceEC210L
Lon to RS232 AdapterECO232
Lon to RS232 Adapter (For HMX PA/VA Systems – No Handshake)EC0232PAVA
Lon to RS232 Adapter (For HMX PA/VA System – 3 Min Time Delay)EC0232PAVA3D
Dual-Channel LonWorks BMS Interface (Non Handshaking)EC200
Dual-Channel LonWorks BMS Interface (Handshaking)EC200H
Dual-Channel LonWorks BMS Interface (Self configuring or use with EC700)EC200S
Lon Network BoosterE540

LONWORKS ADAPTORS

Code:CFSFL01CFSFL02
Description:Single Mode Lon to Fibre Optic AdapterDual Channel Lon to Fibre Optic Adaptor
Operating Voltage:24Vdc24Vdc
Communications Protocol:LonWorksLonWorks
LonWorks Connectors:Screw terminal blockScrew terminal block
LonWorks Rate:78 Kbps / 1.25 Mbps78 Kbps / 1.25 Mbps
Bit Error Rate:1.00E-081.00E-08
Wavelength:1310nm1310nm
Fibre Type:Single mode fibreSingle mode fibre
Fibre Diameter:9/125 micron9 / 125 micron
Fibre Connector:SC type (optional ST type)SC type (optional ST type)
Link Distance:15km15km
Operating Temperature:-30°C to +70°C-30°C to +70°C
Humidity (Non-condensing):20 to 90% RH20 to 90% RH
Dimensions (HxWxD):116mm x 136mm x 34mm116mm x 136mm x 34mm

LONWORKS BMS INTERFACES

Code:EC210LEC200 / EC200H / EC200S
Description:Dual-Channel LonWorks BMS InterfaceDual-Channel LonWorks BMS Interface
Dimensions (HxWxD):86mm x 105mm x 58mm86mm x 105mm x 58mm
Standards:CECE / UL compliant
Supply Voltage:12Vdc to 30Vdc12Vdc to 30Vdc
Supply Current:<30mA<30mA
Transceivers:Echelon FT5000 / FT-X1Echelon FT5000 / FT-X1
Baudrate:78kbs78kbs
Connectors:5mm screw terminals5mm screw terminals
Enclosure:ABS DIN Rail MountingABS DIN Rail Mounting

LON NETWORK ADDRESSABLE BOOSTER

Code:EC540
Description:Lon Network Booster
Operating Voltage:9Vdc to 35Vdc / 9Vac to 24Vac
Enclosure:DIN43 880
Dimensions (HxWxD):60mm x 105mm x 86mm
Ingress Protection:IP40 (enclosure)
IP20 (screw terminals)
Installation:DIN Rail mounting or wall mounting

DOWNLOADS

TEL: 254-774-211313

close
Start typing to see posts you are looking for.
Set your categories menu in Theme Settings -> Header -> Menu -> Mobile menu (categories)

Shopping cart

close
Scroll To Top