Lon to RS232 Adapter (for HMX PA/VA system – no handshake) – EC0232PAVA

The EC0232PAVA offers a similar interfacing facility to the HMX PA/VA (public address/voice alarm) system by withholding the handshaking functionality, and if required the EC0232PAVA3D offers an additional 3 minute time delay before the voice alarm function is actuated. The bi-directional link allows the status of the HMX PA/VA system to be displayed and monitored at the control panel. Different messages may be played depending on the configuration of the cause and effect programming.

The interface may be located anywhere on the Cooper peer to peer network allowing information from any intelligent addressable control panel to be routed through the bi-directional RS232 port to PC or PA/VA system.

Additional information
Order Code

EC0232PAVA

System

Addressable

Product Type

Addressable Network and BMS

Contact me about this Product
Name
Email
Phone
Enquiry

COMPREHENSIVE

Full range to suit addressable fire system requirements

SOFT ADDRESSING

Helps monitor & manage building management systems (BMS)

USER-FRIENDLY

Easy to install, use and diagnose issues

Single Mode Lon to Fibre Optic AdaptorCFSL01
Dual Channel Lon to Fibre Optic AdapterCFSFL02
Dual Channel LonWorks BMS InterfaceEC210L
Lon to RS232 AdapterECO232
Lon to RS232 Adapter (For HMX PA/VA Systems – No Handshake)EC0232PAVA
Lon to RS232 Adapter (For HMX PA/VA System – 3 Min Time Delay)EC0232PAVA3D
Dual-Channel LonWorks BMS Interface (Non Handshaking)EC200
Dual-Channel LonWorks BMS Interface (Handshaking)EC200H
Dual-Channel LonWorks BMS Interface (Self configuring or use with EC700)EC200S
Lon Network BoosterE540

LONWORKS ADAPTORS

Code:CFSFL01CFSFL02
Description:Single Mode Lon to Fibre Optic AdapterDual Channel Lon to Fibre Optic Adaptor
Operating Voltage:24Vdc24Vdc
Communications Protocol:LonWorksLonWorks
LonWorks Connectors:Screw terminal blockScrew terminal block
LonWorks Rate:78 Kbps / 1.25 Mbps78 Kbps / 1.25 Mbps
Bit Error Rate:1.00E-081.00E-08
Wavelength:1310nm1310nm
Fibre Type:Single mode fibreSingle mode fibre
Fibre Diameter:9/125 micron9 / 125 micron
Fibre Connector:SC type (optional ST type)SC type (optional ST type)
Link Distance:15km15km
Operating Temperature:-30°C to +70°C-30°C to +70°C
Humidity (Non-condensing):20 to 90% RH20 to 90% RH
Dimensions (HxWxD):116mm x 136mm x 34mm116mm x 136mm x 34mm

LONWORKS BMS INTERFACES

Code:EC210LEC200 / EC200H / EC200S
Description:Dual-Channel LonWorks BMS InterfaceDual-Channel LonWorks BMS Interface
Dimensions (HxWxD):86mm x 105mm x 58mm86mm x 105mm x 58mm
Standards:CECE / UL compliant
Supply Voltage:12Vdc to 30Vdc12Vdc to 30Vdc
Supply Current:<30mA<30mA
Transceivers:Echelon FT5000 / FT-X1Echelon FT5000 / FT-X1
Baudrate:78kbs78kbs
Connectors:5mm screw terminals5mm screw terminals
Enclosure:ABS DIN Rail MountingABS DIN Rail Mounting

LON NETWORK ADDRESSABLE BOOSTER

Code:EC540
Description:Lon Network Booster
Operating Voltage:9Vdc to 35Vdc / 9Vac to 24Vac
Enclosure:DIN43 880
Dimensions (HxWxD):60mm x 105mm x 86mm
Ingress Protection:IP40 (enclosure)
IP20 (screw terminals)
Installation:DIN Rail mounting or wall mounting

Benefits

. Integrates PC based applications

. Integrates PA/VA systems, site monitor and graphpack

. Flexibility to use any PC application

Features

. Allows connection of Cooper system network devices to PC based applications

. Can be connected at any point on peer to peer network

. Allows Cooper system network to be connected to PC or PA/VA

Single Mode Lon to Fibre Optic AdaptorCFSL01
Dual Channel Lon to Fibre Optic AdapterCFSFL02
Dual Channel LonWorks BMS InterfaceEC210L
Lon to RS232 AdapterECO232
Lon to RS232 Adapter (For HMX PA/VA Systems – No Handshake)EC0232PAVA
Lon to RS232 Adapter (For HMX PA/VA System – 3 Min Time Delay)EC0232PAVA3D
Dual-Channel LonWorks BMS Interface (Non Handshaking)EC200
Dual-Channel LonWorks BMS Interface (Handshaking)EC200H
Dual-Channel LonWorks BMS Interface (Self configuring or use with EC700)EC200S
Lon Network BoosterE540

LONWORKS ADAPTORS

Code:CFSFL01CFSFL02
Description:Single Mode Lon to Fibre Optic AdapterDual Channel Lon to Fibre Optic Adaptor
Operating Voltage:24Vdc24Vdc
Communications Protocol:LonWorksLonWorks
LonWorks Connectors:Screw terminal blockScrew terminal block
LonWorks Rate:78 Kbps / 1.25 Mbps78 Kbps / 1.25 Mbps
Bit Error Rate:1.00E-081.00E-08
Wavelength:1310nm1310nm
Fibre Type:Single mode fibreSingle mode fibre
Fibre Diameter:9/125 micron9 / 125 micron
Fibre Connector:SC type (optional ST type)SC type (optional ST type)
Link Distance:15km15km
Operating Temperature:-30°C to +70°C-30°C to +70°C
Humidity (Non-condensing):20 to 90% RH20 to 90% RH
Dimensions (HxWxD):116mm x 136mm x 34mm116mm x 136mm x 34mm

LONWORKS BMS INTERFACES

Code:EC210LEC200 / EC200H / EC200S
Description:Dual-Channel LonWorks BMS InterfaceDual-Channel LonWorks BMS Interface
Dimensions (HxWxD):86mm x 105mm x 58mm86mm x 105mm x 58mm
Standards:CECE / UL compliant
Supply Voltage:12Vdc to 30Vdc12Vdc to 30Vdc
Supply Current:<30mA<30mA
Transceivers:Echelon FT5000 / FT-X1Echelon FT5000 / FT-X1
Baudrate:78kbs78kbs
Connectors:5mm screw terminals5mm screw terminals
Enclosure:ABS DIN Rail MountingABS DIN Rail Mounting

LON NETWORK ADDRESSABLE BOOSTER

Code:EC540
Description:Lon Network Booster
Operating Voltage:9Vdc to 35Vdc / 9Vac to 24Vac
Enclosure:DIN43 880
Dimensions (HxWxD):60mm x 105mm x 86mm
Ingress Protection:IP40 (enclosure)
IP20 (screw terminals)
Installation:DIN Rail mounting or wall mounting

DOWNLOADS

TEL: 254-774-211313

close
Start typing to see posts you are looking for.
Set your categories menu in Theme Settings -> Header -> Menu -> Mobile menu (categories)

Shopping cart

close
Scroll To Top